Free Call Australia : 1 800 834 991

Related Products

Iskra WS 0014 Energy Meters for Rail Mounting

ISKRA WS 0014 Energy Meters for Rail Mounting 
  • The meter measures active energy directly in a 2-wire network
  • Meter accuracy class is 1, according to the IEC 62053-21 standard
  • Single phase direct connected DIN-rail mounting meter & Maximum current 45 A (Imax)

Product Details

ISKRA WS 0014 Energy Meters for Rail Mounting

WS 0014 is an electronic single phase active energy meter. The meter measures active energy directly in a 2-wire network. Meter accuracy class is 1, according to the IEC 62053-21 standard for active energy meter. The meter can be mounted on a DIN rail (1-pitch).

Features:

• Single phase direct connected DIN-rail mounting meter

• Class 1 according to IEC 62053-21

• Maximum current 45 A (Imax)

• Basic current (Ib) 5 A

• Starting current 0,004 Ib

• 230 V rated system voltage input (Un)

• Voltage operating range -30% ... +30% Un

• Reference frequencies 50 or 60 Hz

• Power consumption circuit < 8 VA , =0.4W

• Temperature range as indoor meter according to IEC 62052-11

• 7-digit LCD (5+2) 99999.99kWh

• LED rate for energy flow 1000 imp/kWh

• Pulse output 1000 imp/kWh:
- Voltage 12 ~ 27V, Current =27mA
- Impulse width=90ms
- Limits of values: max 60VDC, max 50mA

ISKRA WS 1302 Energy Meters for Rail Mounting The WS 1302 energy meter is used for measuring energy in three-phase systems and comes equipped with an LCD display . It is a transformer-ope...
ISKRA WS 0102 Energy Meters for Rail Mounting The WS 0102 energy meter is used for measuring energy in three-phase systems. It has a double 7-digit energy counter. The WS 0102 can be conn...
ISKRA WS 0101 Energy Meters for Rail Mounting The WS 0101 energy meter is used for measuring energy in three-phase systems. It has a 6+1-digit energy counter. The WS 0101 can be connected...
ISKRA WS 0302 Energy Meters for Rail Mounting The WS 0302 energy meter is used for measuring energy in three-phase systems. It has double 7-digit energy counter. It is a transformer opera...
ISKRA EC1-80 Energy Meters for Rail Mounting Active energy meters for single-phase alternating current with 8 digits (1 decimal) digital counters. These meters have 2 S0 interface generat...